4Way Sway Bracing
Install the Longitudinal and Lateral Sway Bracing together because piping can be affected by both horizontal and vertical seismic effects.
- Installable angle: 30˚ ~ 90˚
- Installation piping specifications: 50A ~ 200A
- Low ceiling and CPVC a combined use Inventory management is easy
- Minimum installation height 173 mm
- Convenient visual identification via bolt head

Support length(KS) | Support length | 30˚ ~ 44˚(Nm) | 45˚ ~ 59˚(Nm) | 60˚ ~ 74˚(Nm) | 75˚ ~ 90˚(Nm) |
---|---|---|---|---|---|
50A | 3,200 | 2,224 | 3,145 | 3,852 | 4,448 |
65A | 3,200 | 2,224 | 3,145 | 3,852 | 4,448 |
80A | 3,200 | 2,224 | 3,145 | 3,852 | 4,448 |
100A | 3,200 | 2,224 | 3,145 | 3,852 | 4,448 |
125A | 3,200 | 3,559 | 5,033 | 6,164 | 7,117 |
150A | 3,200 | 3,559 | 5,033 | 6,164 | 7,117 |
200A | 3,200 | 4,482 | 6,338 | 7,763 | 8,963 |
4Way Sway Bracing (Perpendicular)
Installed in a vertical fire main pipe without exceeding the maximum spacing of 8 m between braces If the 4Way Sway Bracing on the top of the bridge is attached to the horizontal pipe, it should be installed within 0.6 m from the center line of the bridge. Install at the end of vertical fire main piping if exceeding 1m.
4Way Sway Bracing (level)
- 4Way Sway Bracing installed within 1.8m of seismic isolation system
- 4Way Sway Bracing is used for side and longitudinal displacement