Longitudinal Sway Bracing

Longitudinal Sway Bracing

A device to prevent pipe breakage caused by excessive shaking in case of earthquake Installed in the fire main and cross piping without exceeding the maximum interval of 24m between the braces, and the distance between the last brace and the end does not exceed 12m.

KFI-rev1 
인정 번호 버팀 18-15

Installable angle: 30˚ ~ 90˚
              Installation piping specifications: 50A ~ 200A

 
  • Low ceiling and CPVC a combined use Inventory management is easy
  • Minimum installation height 173 mm
  • Convenient visual identification via bolt head
unnamed file
Longitudinal Sway Bracing

제품 정격하중

Support length(KS) Support length 30˚ ~ 44˚(Nm) 45˚ ~ 59˚(Nm) 60˚ ~ 74˚(Nm) 75˚ ~ 90˚(Nm)
50A 3,200 2,224 3,145 3,852 4,448
65A 3,200 2,224 3,145 3,852 4,448
80A 3,200 2,224 3,145 3,852 4,448
100A 3,200 2,224 3,145 3,852 4,448
125A 3,200 3,559 5,033 6,164 7,117
150A 3,200 3,559 5,033 6,164 7,117
200A 3,200 4,482 6,338 7,763 8,963