4Way Sway Bracing

4Way Sway Bracing

Install the Longitudinal and Lateral Sway Bracing together because piping can be affected by both horizontal and vertical seismic effects.

무제-3

  • Installable angle : 30˚ ~ 90˚
  • Installation piping specifications : 50A ~ 200A
  • Low ceiling and CPVC a combined use Inventory management is easy
  • Minimum installation height 173 mm
  • Convenient visual identification via bolt head
Shear bolt

Shear bolt

Seismic anchor bolts

Seismic anchor bolts

CPVC combined use

CPVC combined use

Low ceiling

Low ceiling

4Way Sway Bracing (Perpendicular)

Installed in a vertical fire main pipe without exceeding the maximum spacing of 8 m between braces If the 4Way Sway Bracing on the top of the bridge is attached to the horizontal pipe, it should be installed within 0.6 m from the center line of the bridge. Install at the end of vertical fire main piping if exceeding 1m.

4Way Sway Bracing (level)

  • 4Way Sway Bracing installed within 1.8m of seismic isolation system
  • 4Way Sway Bracing is used for side and longitudinal displacement